Multicore Flexible Cable for Application & Machine tools
Technical Specification
Type of Insulation | Type of Sheathing | Application Standards | Typical Application |
Standard PVC | Standard PVC, HRPVC | IS 694 | Power Cords for appliance, Power supplies Connection to various electrical components. Multi core flexible cables are used in various small & big Industrial |
Heat Resistant PVC upto 105° | Standard PVC, HRPVC | IS 694 | Hi-power appliances, ovens, temporary power supply in highter temperature areas |
Standard PVC of FRLS | FRLS (Flame-retardant Low Smoke) | IS 694 | Power Cords for application used in fire prone areas, flame proof equipments, machine tools used in critical locations and heat zones. |
Nominal Cross Sectional Area of Conductor | Number/ Nom.Dia of cond. Stands | Thikness Nominal of Insulator Two (Nom) Core |
Nominal Thickness of Sheath | Appox. Overall Diameter | Current Rating A.C | Voltage Drop/ Amp./Meter | Max. Conductor Resistance per KM at 20°C | |||||
Two Core | Three Core | Four Core | Two Core | Three Core | Four Core | DC or Single Phase AC | 3 Phase AC | |||||
Sq. mm | mm | mm | mm | mm | mm | mm | mm | mm | Amps | mV | mV | Ohms |
0.5 | 16/0.20 | 0.6 | 0.9 | 0.9 | 0.9 | 6.2 | 6.6 | 7.2 | 6 | 83 | 72 | 39.0 |
0.75 | 24/0.20 | 0.6 | 0.9 | 0.9 | 0.9 | 6.5 | 6.9 | 7.6 | 9 | 56 | 48 | 26.0 |
1.0 | 32/0.20 | 0.6 | 0.9 | 0.9 | 0.9 | 6.9 | 7.3 | 8.2 | 14 | 43 | 37 | 19.5 |
1.5 | 30/0.25 | 0.6 | 0.9 | 0.9 | 1.0 | 7.8 | 8.2 | 9.3 | 18 | 31 | 26 | 13.3 |
2.5 | 50/0.25 | 0.7 | 1.0 | 1.0 | 1.0 | 9.0 | 9.6 | 10.5 | 24 | 18 | 16 | 7.98 |
4.0 | 56/0.30 | 0.8 | 1.0 | 1.0 | 1.0 | 10.3 | 10.9 | 12.3 | 32 | 11 | 9.6 | 4.95 |